Skip to content

Gas Lift Valve Design Tutorial

1. Objective

Determine optimal gas-injection volume and depth, space mandrels, and size valve ports.

Process overview

Gas Lift Valve Ordering and Behavior

The gas lift valves are ordered by descending measured depth with valve number. The deepest valve is valve #1, the second deepest is #2, and so on. If Last Valve Always Open is ticked, then PSC and PSO for valve 1 (if specified) will be disregarded by the calculator.

2. Getting Started

  1. Open SNAPFile → Open, then open the example file:
    C:\Program Files (x86)\SNAP\8aGLSURV.snp.
  2. Page through each panel to familiarize yourself with the raw input data.
  3. Run the case and review the results.

3. Choose Injection Depth

The depth sensitivity implies “the deeper the better.” Go to the Gas Lift panel and place the injection point as low as physically possible (start with 8900 ft TVD).

Set injection depth

4. Run a GLR Sensitivity

After confirming that lower injection depth is better, go to Sensitivities and run a sensitivity on Gas Lift GLR.

Set GLR sensitivity

What you see indicates significant variance in lift with GLR, so plot the sensitivity graph:

GLR sensitivity setup

GLR sensitivity result

5. Interpret the Sensitivity

The well only needs about 1200 GLR before it starts overlifting (oil rate no longer increases with GLR). Use ~1200 GLR as a starting point for detailed design.

1200 GLR clue

6. Estimate Design Targets

On the Gas Lift Design page you can estimate potential liquid rate and required injection pressure.

For this case, design for TVD 8900 ft, operating injection pressure > 1080 psia, and liquid rate 500 BLPD.

Initial design targets

7. Switch to Gas-Lift Design Mode

Return to the General tab and check Gas Lift Design.

Enable Gas Lift Design

Page forward (Next) until you reach the Gas Lift Design page.

Gas Lift Design page

8. Enter Initial Design Parameters

Enter your best estimates. The Kick-off pressure should be well above the ~1082 psia operating pressure to allow step-down through the valves. Enter 500 BLPD, or click Import near the objective Liquid Rate to pull it from the prior solution.

The nodal plot indicates the well can produce 500 BLPD, but your lift system must have sufficient lift pressure and gas rate to match the design.

Nodal target reminder

9. Set Default Injection Depth and Apply

If the default injection depth is not at the design lift point, adjust the single default valve to that depth (e.g., 8900 ft).

Adjust default valve depth

Press Apply to see the case without detailed valve data.

Case apply (no detailed valves)

You have sufficient lift-gas volume and pressure to lift to the design depth. Assume 1250 psia available for now (higher pressures lift greater volumes but may not require unloading valves).

Survey “crosses” on the gradient plot help check hydraulics at the survey conditions. A kink near 8900 ft suggests lifting at that location. After changing rate/GLR/depth, do not expect the survey to match.

Survey crosses vs. gradient

Save the dataset under a new name for valve design work.

10. Mandrel Spacing Utility

Re-open the Gas Lift panel → Valve Design tab. You’ll see one default valve at 8900 ft (it will be discarded when spacing is computed). Click Mandrel Spacing Utility.

Mandrel Spacing Utility button

Set preferences (max injection depth, design options).

Spacing preferences

When you click Do Spacing Line Design Method, you’ll be reminded the design is approximate and must be independently reviewed for accuracy and suitability.

Approximation notice

The program generates spacing (about 6 valves typical) based on your inputs and local preferences. Slight differences from the screenshots are expected.

Generated spacing

11. Post Test-Rack Pressures and Update

Before reviewing the design plot, post the design Test-rack pressures to the case and Apply.

BEFORE pressing “Update PVO”:

Update PVO — before and after

AFTER pressing:

After Update PVO

The design plot now shows the operating pressure (e.g., 927 psia) in the header.

Design plot

12. Finalize Valve and Port Details

Return to the Valve Design tab and adjust to the actual valves you plan to purchase.
Adjust port sizes so the Gas-lift report shows each valve passing the required gas at its location. For this case, you may need 1.5" mandrels to pass sufficient gas at the required rates/volumes.

1) Use the Gas-lift Kick-off simulator to tune required lift-gas rates at each valve and determine needed port sizes.
Kick-off simulator

2) Ensure the black operating condition line appears on the plot so you can confirm the orifice is passing the design amount.

3) Add extra mandrels for unanticipated conditions and test scenarios. Dummy off unneeded mandrels. Click Interpolate Temps and Update MD to align with correct gyro locations.
Extra mandrels & checks

13. Known Limitations in This Simple Design

1) It is not possible to move enough gas through the top valve to reach the second location with a 1" mandrel.
2) The orifice already uses the largest port, so there is no option to up-size.

This technology is best applied by experienced designers, but this short tutorial demonstrates the inputs and decisions involved in a typical valve-design workflow.